Data centers

Flooring engineered for static control and uninterrupted uptime

Static-dissipative, low-outgassing systems for server halls, battery rooms, and support spaces.

The Environment

Data centers place demands on a floor that few other environments do. Sensitive electronics sit inches above the slab, racks and PDUs concentrate heavy point loads on small footprints, and the facility never shuts down for a floor replacement. Add to that the low relative humidity most halls run at, and static control stops being a nice-to-have and becomes an equipment-protection issue. Kretus ESD is a permanently static-dissipative system that carries charge to ground through the matrix itself rather than relying on a topical treatment. Because performance is built into the material, it does not fall off as the air dries out or as the floor is cleaned over time.

Primary Systems

Nanotube ESD, Industrial Sand, Color Chip

Spec Section

09 67 23

Environment Requirements

1

Static discharge

Charge generated by people and carts arrives at equipment that cost more than the building shell.

2

Low humidity

Halls run dry. Floors that depend on ambient moisture to conduct stop working exactly when you need them.

3

Point loading

Rack feet and PDU casters concentrate several tons onto a few square inches of slab.

4

No shutdown window

Installation happens around live equipment, in phases, with cure times that fit a maintenance window.

5

Particulate and outgassing

Seamless, non-shedding surfaces keep contamination out of air handling and off boards.

6

Slab moisture vapor

Vapor drive through a slab-on-grade will delaminate a floor that was specified without testing for it.

7

Light reflectance

A brighter floor lets you hit target lux with fewer fixtures, which is load you do not have to cool.

8

Cleaning and retest

The wrong cleaner leaves an insulating film, and a floor that tested correctly at handover quietly stops performing.

Zone and System Schedule
Zone
Recommended System
Governing Conditions
White space / server hall
ESD (Static Control)
Live IT equipment, low relative humidity, concentrated point loads under rack feet and PDUs, cart and lift traffic during deployments, strict particulate limits.
UPS and battery room
ESD (Static Control)
Sulfuric acid or electrolyte exposure, spill containment requirements, heavy static battery cabinet loads, limited traffic.
Generator room and fuel storage
Industrial Sand
Diesel and lubricant exposure, thermal cycling, vibration, occasional heavy maintenance equipment, secondary containment requirements.
Electrical rooms and switchgear
ESD (Static Control)
Arc flash safety considerations, technician work on energized gear, light foot traffic, occasional equipment rolling.
Network operations center
Color Chip
Occupied 24/7, appearance matters, acoustics and comfort underfoot, low traffic volume, client tours.
Loading dock and staging
Industrial Sand
Pallet jacks, forklifts, dropped crates, thermal shock at exterior doors, unboxing debris, the highest abuse in the building.
Chiller plant and mechanical rooms
Industrial Sand
Standing water and condensation, glycol and treatment chemical exposure, floor drains, wet slip risk, heavy equipment pads.
Corridors and circulation
ESD (Static Control)
High foot and cart traffic, transitions between controlled and uncontrolled zones, cleaning equipment.
configuration
standard
result
limit
outcome
Epoxy Dissipative
ANSI/ESD STM7.1
1.0 x 10^6 to <1.0 x 10^9 ohms
<1.0 x 10^9 ohms
PASS
Epoxy Conductive
ANSI/ESD STM97.1
<1.0 x 10^9 ohms
<1.0 x 10^9 ohms
PASS
Poly Dissipative
ANSI/ESD STM7.1
1.0 x 10^6 to <1.0 x 10^9 ohms
<1.0 x 10^9 ohms
PASS
Poly Conductive
ANSI/ESD STM7.1
2.5 x 10^4 to <1.0 x 10^6 ohms
<1.0 x 10^9 ohms
PASS
Standards and Test Methods

Kretus epoxy and poly ESD flooring met ANSI/ESD S20.20 qualification testing for Commercial, Space and Defense protocols. Every figure below carries its method, limit, and test conditions.